Overview
Product Attributes

Model No.WCP2.5~WCP45

BrandAmrta or OEM

TypeWater-Cooled

Cooling MethodWater-cooled

Unit StructureIntegral

Selected Voltage220V/50HZ

Compressor Number1

Noise LevelOrdinary

CertificationCE

ColourWhite

Application FieldsMechanical Engineering, School, Airport, Shopping Mall, Industrial Buildings

RefrigerantR410A/R407c/R134A/R22

Electric PartsSchneider Brand

Refrigerant ValvesDanfoss/Emerson Brand

Unit TypeCooling Only/Heat Pump/Cooling Only With Electric Heater

Compressor BrandDanfoss/Copeland/Panasonic/Daikin

Cooling Capacity2.5kW To 45kW

ControllerSaturn Brand Or Siemens PLC(optional)

Power Supply220V-1PH-50HZ/60HZ, 230V-1PH-60HZ

Supply Ability & Additional Information

PackagingPlywood Casing or standard package suitable for sea and air transport

Productivity6000PCS/Year

TransportationOcean,Air

Place of OriginChina

Supply Ability500PCS/Month

HS Code8418612090

PortQingdao,Shandong,China

Payment TypeL/C,T/T,Western Union

IncotermFOB,CFR,CIF

Packaging & Delivery
Selling Units:
Set/Sets
Package Type:
Plywood Casing or standard package suitable for sea and air transport

Heat Pump Water to Air Chiller use cycle water as heat source, could be in heating and cooling mode, it is high efficiency energy saving central Air Conditioning technique. When in cooling, use the cycle water as exhaust heat source. When in heating, use the cycle water as absorb heat sourceThe Heat Pump Water to Air Chiller installation should be stable and firm, no vibration. Should not install the Heat Pump Air Conditioner on the site where the people often stay there, should install in the path, store room or bathroom.


Why this choice?
● Saving space
● Galvanised steel construction
● AMWCP are well insulated to minimise condensation and attenuate noise.

Application areas
● Offices, Hotels, Hospitals
● Administration
● Industry
●Commercial buildings


Characteristics

01. StructureGalvanised steel construction, closed cell foam lined compressor and fan compartments, with an insulted and powder coated drain tray for complete moisture protection, the drain tray is easily removed for inspection and cleaning. 

02. Refrigerant. Each unit is factory charged with refrigerant R410a, which is deemed to have zero ozone depletion potential.

03. Hermetic compressor. Single phas rotary compressor is used for this type unit, with built-in thermal overload cut-out, mounted on rubber vibratrion damperss.

04. Centrifugal Fan. High efficiency, double inlet centrifugal fan protection level IP44. Low noise, low speed, big air flow and high ESP.
05. Water side heat exchanger. high efficiency coaxial heat exchanger, factory insulated with flexible close cell material.
06. Air Filter. An optional filter integrated return air spigot is available on all models.The filter is a washable polypropylene netmedia. Care should be taken, when locating each unit, that to enough space is provided to enable the one-piece filter to be withdrawn to its full length from either side of the unit.
07. Insulation. AMTKWP are well insulated to minimise condensation and attenuate noise.

08. Electric Heater(Optional). Electric heater is optional on cooling only versions. Electric elements have spirally wound stainless steel fins to give increased area and low surface temperature. They are totally enclosed within the unit and are supplied with safety cutouts. An optional fan run-on timer for rapid heat dissipation is available.
09. Electric Panel
Consists of:
Compressor contactor
Compressor protection breaker
Microprocessor with function display
10. All Models are Equipped with Wire Controller with the Following Features
7 days programmable timer
Auto random restart
Error self diagnostic
11. Safety Protection
High pressure switch
Low pressure switch
Discharge temperature protection
Anti freezing protection


Specification

Model / WCP3.5 WCP5 WCP7 WCP9 WCP12 WCP14
Power supply V/Ph/ Hz 220- 240v/1/50




Cooling
Capacity KW 3.6 5.0 7.25 9.3 12.3 14.8
Sensible cooling capacity KW 2.9 3.7 5.61 7.2 9.48 11.8
Power Input KW 1.02 1.24 2.0 2.58 3.02 4.05
Rated current A 4.40 5.83 9.25 11.5 13.3 18.0
AEER W/W 3.6 3.73 3.65 3.8 4.29 3.86


Heating
Capacity KW 3.82 5.7 7.89 10.2 12.7 15.5
Input KW 1.07 1.4 2.20 2.65 3.28 4.34
Rated current A 4.8 6.35 9.81 11.9 14.43 19.2
ACOP W/W 3.57 4.01 3.60 3.83 3.86 3.59
Max. input consumption KW 1.4 2.4 2.66 4.0 4.2 5.7
Max. current A 6.0 10.0 11.38 17.1 18.0 19.2
Starting current A 20 28 30 40 35 42
External static pressure at (Hi) Pa 60 60 100 120 120 150
Indoor air flow (Hi) l/sec 194 278 378 472 639 750
Indoor noise level(Hi) dB(A) 42 44 45 47 50 52


Dimension
W mm 1250 1250 1250 1360 1685 1820
H mm 445 445 445 495 445 445
D mm 751 800 800 800 800 850
Net Weight kg 75 86 100 103 115 160
water in the water side exchanger kg 0.80 0.86 1.50 1.87 2.20 2.66

Compressor
Type / Rotary Rotary Rotary Rotary Rotary Rotary
Quantity / 1 1 1 1 2 2
Water flow l/sec 0.22 0.29 0.44 0.58 0.73 0.89
Diameter of water in/out pipe   DN20 DN20 DN20 DN25 DN25 DN25
Diameter of drain pipe inch 1 1 1 1 1 1
Refrigerant control   TXV TXV TXV TXV TXV TXV
Condsate lift pump(option) Flow rate ml/min 2500 2500 2500 2500 2500 2500
Lift height m 4.5 4.5 4.5 4.5 4.5 4.5
Water coil pressure drop kpa 25 40 41 40 51 91

Refrigerant
Type / R410a R410a R410a R410a R410a R410a
Charge g 750 950 1150 1500 1000*2 1150*2

Drain tray
Material / Stainless steel
Insulation Material / 5mm PE

01. Norminal cooling capacity test condition: Water side water inlet/outlet 30ºC/35ºC, Ambient temperature DB 27 ºC, WB 19 ºC.
02. Norminal heating capacity test condition: Water side water inlet 20ºC, Ambient temperature DB 20 ºC, WB 15 ºC.
03. Noise level measured in the noise lab with background noise of 25 dB(A), at a distance of 1 m.
04. As our continuous products improvement, Amrta reserves the right to change specifications and design without notice.

Heat Pump Air ConditioningHeat Pump Commercial Chiller

Product Categories : Heat Pump System > Water To Air Heat Pump

Download
Home > Products > Heat Pump System > Water To Air Heat Pump > Water Source Heat Pump Unit
Email to this supplier
  • *Subject:
  • *To:
    Mr. Richard Lee
  • *Email:
  • *Message:
    Your message must be between 20-8000 characters
Send Inquiry
*
*

Related Products List

Home

Product

Whatsapp

About Us

Inquiry

We will contact you immediately

Fill in more information so that we can get in touch with you faster

Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.

Send