Designed to control the distribution of conditioned air by a 1 way or 4 way louver discharge system, is the most popular solution that allows free floor or wall surfaces. Cassette Fan Coil Unit have been designed to control the distribution of conditioned air by a 1way or 4 way louver discharge system. These types of units are normally located in the false ceiling, with only the front panel visible. With the return air centralized adjustable louvers on the perimeter allow for airflow control in heating and cooling modes. The most popular applications are office buildings and shops. Since the installation is located in the ceiling cassettes are the preferred solution when the user wants a discreet heating and cooling solution that allows free floor or wall surfaces.
Product Description
Efficient and energy saving
Efficient ABS blower which is light weighted while statically and dynamically balanced.
Excellent thinwall copper tube and efficient hydrophilic aluminum fin are under water pressure bonded treatment. Patent inverse crossing circuit to reach the best heat transfer efficiency. Brass water distributor is used for improving water flow distribution, in order to provide better heat transfer effect.
Quiet Operation
Low noise and permanent capacity motor, unique ABS centrifugal blower, all of them pass dynamically balance test, to ensure unit operate quietly and efficiently.
3-speed motor, ball bearing, long lifespan; rubber vibration isolator reduces operation noise.
Stable and Reliable
U-shaped tube bending, reducing soldered dot and leakage point.
Drain pan is made of high grade stainless steel plate, modeling processing; surface has been under hot dipped electroforming painting treatment. 7mm PE thermal insulation foam is applied on the drain pan to prevent condensation and leakage from occurring. Furthermore the width and length of the drain pan has been specifically designed to accommodate the water drop from the water inlet / outlet and electrically operated valve.There is fuse in power supply inlet side to prevent motor burned because of wrong wiring. Reliable and stable motor which enjoys good reputation in the market.
Different Models
Static pressure: 12Pa, 30Pa, 50Pa.
Fan Coil unit series: horizontal exposed type, horizontal concealed type, vertical concealed type, vertical exposed type, cassette type, large air volume fan coil unit.
Accessories: 3-speed switch, return air box, extended drain pan, electronic two-way valve, electrical heater, air cleansing module.
All above are for your selection.
Performance Parameter
Model | 34KM | 51KM | 68KM | 85KM | 102KM | 136KM | 170KM | 204KM | 238KM | |
Air flow [m3/h] | H | 340 | 510 | 680 | 850 | 1020 | 1360 | 1700 | 2040 | 2380 |
M | 280 | 390 | 520 | 640 | 790 | 1030 | 1290 | 1500 | 1800 | |
L | 180 | 260 | 350 | 430 | 520 | 690 | 860 | 1030 | 1200 | |
Total cooling capacity * [W] | H | 2000 | 3000 | 3700 | 5000 | 5600 | 7300 | 9900 | 11000 | 12800 |
Heating capacity * [W] | H | 3000 | 4800 | 5500 | 7200 | 8200 | 10800 | 14500 | 16800 | 19200 |
Fan motor |
|
|
|
|
|
|
|
|
|
|
Nominal power input | W | 37 | 52 | 62 | 76 | 96 | 132 | 152 | 189 | 220 |
Nominal current input | A | 0.162 | 0.23 | 0.276 | 0.338 | 0.417 | 0.588 | 0.663 | 0.824 | 0.976 |
Water flow rate | m3/h | 0.42 | 0.522 | 0.62 | 0.86 | 0.98 | 1.22 | 1.58 | 1.92 | 2.2 |
Water pressure drop | kPa | 14 | 14 | 16 | 18 | 22 | 25 | 39 | 44 | 44 |
Water connections | inch | ZG 3/4`` | ||||||||
Drain pipe | mm | 26 | ||||||||
Sound pressure level ** [dB(A)] | H | 37 | 39 | 41 | 43 | 45 | 46 | 47 | 50 | 52 |
M | 34 | 36 | 38 | 39 | 42 | 43 | 44 | 46 | 48 | |
L | 30 | 32 | 35 | 36 | 38 | 39 | 40 | 42 | 44 | |
Net Dimension W/D/H mm | Unit | 580*580*290 | 710*710*290 | 832*832*290 | ||||||
Panel | 680*680*30 | 830*830*30 | 980*980*30 | |||||||
Power supply | / | 220V/1Ph/50Hz | ||||||||
Net weight kg | Unit | 25 | 25 | 26 | 28 | 29 | 29 | 36 | 38 | 38 |
Panel | 2.5 | 4 | 5 |
Note:* The data are referred to the following conditions:
Cooling: room temperature: 27 ºC, DB / 19.5 ºC WB; water temperature: 7/12 ºC, high speed.
Heating: room temperature: 21 ºC, water inlet temperature: 70 ºC, high speed. Water flow rate same as in cooling operation.
** Sound pressure measured in anechoic room 1.5 m away from the unit.