Model No.: FCU()
Brand: Amrta or OEM
Type: Central Air Conditioners
Usage: Room
Indoor Machine Noise: <23dB
Certification: CE
China Energy Efficiency Standard: Level 1
Cooling/Heating: Cooling/Heating
Power Source: Electrical
Power Type: AC
Condition: New
Packaging: Plywood Casing or standard package suitable for sea and air transport
Productivity: 10000PCS/Year
Transportation: Ocean,Air
Place of Origin: China
Supply Ability: 10000PCS/Month
HS Code: 8415830000
Port: Qingdao,Shandong,China
Payment Type: L/C,T/T,Western Union
Incoterm: FOB,CFR,CIF
Amrta Chilled Water Fan Coil Unit provide maximum performance, unparalleled design flexibility and superior serviceability. The extensive selection of available standard and optional features provides the versatility you need to fit any heating, ventilation and Air Conditioning system design. When install the Fan Coil Unit, please make sure the top level fo the unit horizontal, the drain pan is designed with a little gradient to faciliate drain. For Concealed Type Fan Coil Unit, it can be with Plenum box or without plenum box. Plenum box also called Return air Box.
Product Description
01.Efficient and Energy Saving. Efficient ABS blower which is light weighted while statically and dynamically balanced. Excellent thinwall copper tube and efficient hydrophilic aluminum fin are under water pressure bonded treatment. Patent inverse crossing circuit to reach the best heat transfer efficiency. Brass water distributor is used for improving water flow distribution, in order to provide better heat transfer effect.
02.Quiet Operation.Low noise and permanent capacity motor, unique ABS centrifugal blower, all of them pass dynamically balance test, to ensure unit operate quietly and efficiently. 3-speed motor, ball bearing, long lifespan; rubber vibration isolator reduces operation noise.
03.Stable and Reliable. U-shaped tube bending, reducing soldered dot and leakage point. Drain pan is made of high grade stainless steel plate, modeling processing; surface has been under hot dipped electroforming painting treatment. 7mm PE thermal insulation foam is applied on the drain pan to prevent condensation and leakage from occurring. Furthermore the width and length of the drain pan has been specifically designed to accommodate the water drop from the water inlet / outlet and electrically operated valve.There is fuse in power supply inlet side to prevent motor burned because of wrong wiring. Reliable and stable motor which enjoys good reputation in the market.
04. Different Models Static pressure: 12Pa, 30Pa, 50Pa.
Fan coil Air Conditioner unit series: horizontal exposed type, horizontal concealed type, vertical concealed type, vertical exposed type, cassette type, large air volume fan coil unit. Accessories: 3-speed switch, return air box, extended drain pan, electronic two-way valve, electrical heater, air cleansing module. All above are for your selection.
Performance Parameter
Model | 34WA | 51WA | 68WA | 85WA | 102WA | 136WA | 170WA | 204WA | 238WA | ||
Rated air volume m³/h | H | 340 | 510 | 680 | 850 | 1020 | 1360 | 1700 | 2040 | 2380 | |
M | 255 | 383 | 510 | 638 | 765 | 1020 | 1275 | 1530 | 1785 | ||
L | 170 | 255 | 340 | 425 | 510 | 680 | 850 | 1020 | 1190 | ||
Rated cooling capacity W | H | 1800 | 2700 | 3600 | 4500 | 5400 | 7200 | 9000 | 10800 | 12600 | |
M | 1440 | 2160 | 2880 | 3600 | 4320 | 5760 | 7200 | 8640 | 10080 | ||
L | 1170 | 1755 | 2340 | 2925 | 3510 | 4680 | 5850 | 7020 | 8190 | ||
Rated heating capacity W | H | 2700 | 4050 | 5400 | 6750 | 8100 | 10800 | 13500 | 16200 | 18900 | |
M | 2160 | 3240 | 4320 | 5400 | 6480 | 8640 | 10800 | 12960 | 15120 | ||
L | 1755 | 2633 | 3510 | 4388 | 5265 | 7020 | 8775 | 10530 | 12285 | ||
Input power W | 12Pa | H | 37 | 52 | 62 | 76 | 86 | 134 | 152 | 189 | 228 |
30Pa | H | 44 | 59 | 72 | 87 | 100 | 156 | 174 | 212 | 253 | |
50Pa | H | 49 | 66 | 84 | 100 | 108 | 174 | 210 | 250 | 300 | |
Noise dB(A) | 12Pa | H | 37 | 39 | 41 | 43 | 45 | 46 | 48 | 50 | 52 |
30Pa | H | 40 | 42 | 44 | 46 | 47 | 48 | 50 | 52 | 54 | |
50Pa | H | 42 | 44 | 46 | 47 | 49 | 50 | 52 | 54 | 56 | |
Water volume kg/h | 390 | 550 | 700 | 820 | 910 | 1340 | 1590 | 1800 | 2070 | ||
Water pressure loss kPa | ≤30 | ≤30 | ≤30 | ≤30 | ≤40 | ≤40 | ≤40 | ≤40 | ≤50 | ||
Weight kg | Without plenum box | 12.5 | 14 | 14 | 15.5 | 16.5 | 22.5 | 30 | 33 | 33.5 | |
With plenum box | 14.5 | 16 | 17 | 19.5 | 20.5 | 27.5 | 35 | 38 | 39.5 | ||
Motor | Type | E class insulation, permanent capacitor, 3 speed fan | |||||||||
Qty | 1 | 1 | 1 | 1 | 1 | 2 | 2 | 2 | 3 | ||
Fan | Type | Double inlet, forward curve, multi blades, centrifugal fan | |||||||||
Type | 1 | 2 | 2 | 2 | 2 | 3 | 4 | 4 | 4 | ||
Water connection pipe | 3/4" (DN20) | ||||||||||
Condensed water pipe | 3/4" (DN20) | ||||||||||
Max working pressure | 1.6MPa | ||||||||||
Power supply | AC 220V/50Hz |
Note:
1. Cooling capacity is based on air inlet temperature 27oC DB/19.5oC WB, entering water temperature 7oC, T5oC.
2. Heating capacity is based on air inlet temperature 21oC, entering water temperature 60oC, air flow volume and water flow rate are the same with cooling mode.
3. MPT-Mole pipe thread, FPT-Female pipe thread.
4. ESP for C and F series is 0Pa.
5. For FVE, FVC series, there is no Model 140; the performance parameters of FVE and FVC are the same with FHC.
6. Specifications in this catalog are subject to change without notice.
Model | 34KM | 51KM | 68KM | 85KM | 102KM | 136KM | 170KM | 204KM | 238KM | |
Air flow [m3/h] | H | 340 | 510 | 680 | 850 | 1020 | 1360 | 1700 | 2040 | 2380 |
M | 280 | 390 | 520 | 640 | 790 | 1030 | 1290 | 1500 | 1800 | |
L | 180 | 260 | 350 | 430 | 520 | 690 | 860 | 1030 | 1200 | |
Total cooling capacity * [W] | H | 2000 | 3000 | 3700 | 5000 | 5600 | 7300 | 9900 | 11000 | 12800 |
Heating capacity * [W] | H | 3000 | 4800 | 5500 | 7200 | 8200 | 10800 | 14500 | 16800 | 19200 |
Fan motor |
|
|
|
|
|
|
|
|
|
|
Nominal power input | W | 37 | 52 | 62 | 76 | 96 | 132 | 152 | 189 | 220 |
Nominal current input | A | 0.162 | 0.23 | 0.276 | 0.338 | 0.417 | 0.588 | 0.663 | 0.824 | 0.976 |
Water flow rate | m3/h | 0.42 | 0.522 | 0.62 | 0.86 | 0.98 | 1.22 | 1.58 | 1.92 | 2.2 |
Water pressure drop | kPa | 14 | 14 | 16 | 18 | 22 | 25 | 39 | 44 | 44 |
Water connections | inch | ZG 3/4`` | ||||||||
Drain pipe | mm | 26 | ||||||||
Sound pressure level ** [dB(A)] | H | 37 | 39 | 41 | 43 | 45 | 46 | 47 | 50 | 52 |
M | 34 | 36 | 38 | 39 | 42 | 43 | 44 | 46 | 48 | |
L | 30 | 32 | 35 | 36 | 38 | 39 | 40 | 42 | 44 | |
Net Dimension W/D/H mm | Unit | 580*580*290 | 710*710*290 | 832*832*290 | ||||||
Panel | 680*680*30 | 830*830*30 | 980*980*30 | |||||||
Power supply | / | 220V/1Ph/50Hz | ||||||||
Net weight kg | Unit | 25 | 25 | 26 | 28 | 29 | 29 | 36 | 38 | 38 |
Panel | 2.5 | 4 | 5 |
Note:* The data are referred to the following conditions:
Cooling: room temperature: 27 ºC, DB / 19.5 ºC WB; water temperature: 7/12 ºC, high speed.
Heating: room temperature: 21 ºC, water inlet temperature: 70 ºC, high speed. Water flow rate same as in cooling operation.
** Sound pressure measured in anechoic room 1.5 m away from the unit.
Product Categories : Fan Coil > Wall Mounted Fan Coil
Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.
Fill in more information so that we can get in touch with you faster
Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.