Model No.: RTU12 ~ RTU300
Brand: Amrta or OEM
Type: Chiller
Air Tube Material: Galvanized Sheet
Corrosion Durability: General
Operating Voltage: 380/400 VAC
Noise Level: Low
Mounting: Floor Standing
Lifetime: 15~20 years
Certification: CE
Condition: New
Colour: White
Application Fields: Mechanical Engineering, School, Airport, Shopping Mall, Industrial Buildings
Refrigerant: R410A/R407c/R134A/R22
Compressor: Danfoss/Copeland/Panasonic/Daikin
Cooling Capacity: 12kw-300kw
Electric Parts: Schneider Brand
Refrigerant Valves: Danfoss/Emerson Brand
Controller: Syslab Brand Or Siemens PLC(optional)
Power Supply: 380~415V, 440~460V, 50HZ/60HZ
Unit Type: Cooling Only/Heat Pump/Cooling Only With Electric Heater
Packaging: Plywood Casing or Standard Package Suitable for Sea and Air Transport
Productivity: 6000PCS/Year
Transportation: Ocean,Air
Place of Origin: China
Supply Ability: 500PCS/Month
HS Code: 8418612090
Port: Qingdao,Shandong,China
Payment Type: L/C,T/T,Western Union
Incoterm: FOB,CFR,CIF
Easy installation Rooftop Air Conditioner is what are known as package units in the HVAC system. A package unit is set apart from a split system, which is the common type of central air conditioner / heat pump found in houses. A ducted split Air Conditioner has an outdoor cabinet and an indoor cabinet with different sets of components. With a Rooftop Packaged Unit, all the components are housed in one cabinet stored on the top of the building. Both sets of coils, to release and absorb heat, are in the cabinet along with the compressors and the fans. The rooftop air conditioner unit connects directly into the building's ventilation system to circulate the air. Rooftop units can be configured either as air conditioners, or as heat pump capable of both heating and cooling. With installation of a humidistat on a rooftop unit, it can also control humidity and permit the ventilation of fresh air into the system; this is a benefit that ducted split systems do not have, and it is a great asset for increasing indoor air quality.
Application areas
● Large and light commercial buildings (Retail, Airports, Restaurants, shops, petrol stations)● Industrial buildings and logistic centers
● Wide choice of communication interfaces
Hermetic compressor
High efficiency scroll compressor for the whole range, with built-in thermal overload cut - out and crankcase heater, mounted on rubber vibration dampers.
Centrifugal fan
Forward curve centrifugal fans for air treatment section and axial fans for condensation section.
Electric panel
Electric panel consists of breakers and contactors for compressors and fan motors, phase sequence relay and other necessary protection devices for the main components.
Optional
Economizer with fresh, return air dampers and fresh air hood
Technical Data
Model | RTU45 | RTU50 | RTU60 | RTU75 | RTU90 | RTU105 | ||
Cooling capacity | kW | 44.5 | 50 | 60 | 70 | 90 | 105 | |
Heating capacity | kW | 48.7 | 54.3 | 64 | 75.4 | 96.2 | 113.2 | |
Power supply | 380V / 3Ph / 50HZA | |||||||
Cooling power input | kW | 17 | 19.5 | 22.8 | 26.7 | 32.9 | 39.7 | |
Heating power input | kW | 15.6 | 18 | 21 | 24.8 | 30.4 | 36.7 | |
Start current | A | 168 | 186 | 175 | 199 | 197 | 266 | |
Working current in cooling | A | 31.7 | 35.6 | 39.9 | 48.3 | 61 | 70.6 | |
Working current in heating | A | 29.9 | 33.5 | 37.5 | 45.4 | 57.3 | 66.3 | |
Throttle methods | Thermal expansion valve | |||||||
Circuits | 2 | 2 | 2 | 2 | 3 | 3 | ||
Refrigerant | R410A | |||||||
Compressor | Type | Scroll type 380V / 3Ph / 50HZA | ||||||
Qty | 2 | 2 | 2 | 2 | 3 | 3 | ||
Condenser side | ||||||||
Condenser | Type | Al+copper tube | ||||||
Axial fan | Qty | 1 | 1 | 1 | 1 | 2 | 2 | |
Drive | Direct drive | |||||||
Motor power | kW | 0.25 | 0.37 | 0.37 | 0.55 | 0.75 | 0.75 | |
Air flow | m3 /h | 4600 | 7800 | 7800 | 9000 | 12600 | 12600 | |
Evaporator side | ||||||||
Evaporator | Type | Al+copper tube | ||||||
Centrifugal fan | Qty | 1 | 1 | 1 | 1 | 1 | 1 | |
Motor power | kW | 3 | 3 | 4 | 4 | 5.5 | 5.5 | |
Air flow | m3 /h | 7600 | 8500 | 10900 | 12500 | 16000 | 19500 | |
Drive | Direct drive | Belt drive | ||||||
External static pressure(Pa) | 250 | 250 | 300 | 300 | 300 | 300 | ||
Filter | Aluminum frame filter G3 | |||||||
Noise level dB(A) | 73 | 73 | 73 | 75 | 74 | 75 | ||
Dimension | L | mm | 2268 | 2268 | 2298 | 2298 | 2878 | 2878 |
W | mm | 1440 | 1440 | 1650 | 1650 | 2140 | 2270 | |
H | mm | 1167 | 1167 | 1400 | 1400 | 1964 | 1964 | |
Weight | kg | 750 | 770 | 830 | 860 | 1160 | 1350 |
* Performance values refer to the following conditions:
Cooling: room air temperature 27.0°C DB RH 50%, ambient air temperature 35°C;
Heating: room air temperature 20.0°C DB, ambient air temperature 7°C DB / 6°C WB.
** Noise level measured by adopting average value in the noise lab with background noise of 25 dB(A), at a distance of 1.5m high fan speed.
Installation
Project
Product Categories : Air Conditioner > Commercial Air Conditioner
Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.
Fill in more information so that we can get in touch with you faster
Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.