Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.
Model No.: AW60-260, WW80-160
Brand: Amrta or OEM
Type: Cooling Only With Electric Heater/Cooling Only/Heat Pump
Cooling Method: Air-cooled
Unit Structure: Integral
Selected Voltage: 380V/50HZ
Compressor Number: 2
Noise Level: Low
Certification: CE
Condition: New
Compressor Brand: Copeland / Danfoss / Daikin / Panasonic
Refrigerant: R410A / R407c / R134A / R22
Evaporator: Plate / Shell And Tube
Application Fields: Low Temperature Industry
Power Supply: 380-415V, 440-460V, 50HZ/60HZ
Compressor Qty/Circult: 2/3/4
Casing(Optional): Stainless Steel 304/316
Running Condition: Low Ambient Temperature -20degree C
Packaging: Standard Package for Export Transport
Productivity: 5000SETS/Year
Transportation: Ocean,Air
Place of Origin: China
Supply Ability: 400PCS / Month
HS Code: 8418612090
Port: Qingdao,Shandong,China
Payment Type: L/C,T/T
Incoterm: FOB,CFR,CIF
Industrial Glycol Water Chiller with the cooling capacity from 60kW~260kW. Including Air Cooled Glycol Chiller and Water Cooled Glycol Chiller.This type Glycol Water Chiller can work indenpendently or together with up to 16 slave modulars. The Air Cooled Chiller with compact design, reasonable layout and convenient for installation &maintenance etc. Amrta chillers not only serve Cooling and Heating System, but also cooling machine to make the machine running at a good condition.
Application areas
● Offices, Hotels, Hospitals, Industry
● Administration
● Light commercial and residential buildings
Why this choice?
● Very high efficiency with R410A
● Very low noise operation
● R410A scroll compressors
● Advanced control
● Unit with pump and optional buffer tank
● Very compact for outdoor or indoor installation
Characteristics
The master module can work independently or together with up to 16 slave modules.
Glycol Water Chiller Units with V type heat exchanger: panels, frame and base are made from galvanized steel protected with polyester powder painting to ensure total resistance to atmospheric agents.
3-phase scroll type compressor, with builtin thermal overload cut-out and crankcase heater, mounted on rubber vibration dampers.
External rotor type axial fans, equipped with three phase direct drive motors, low noise 8 poles, protection level IP54, provided with a protective outlet grille.
Evaporator built with high efficiency shell and tube type heat exchanger, factory insulated with flexible close cell material.
Condenser built with seamless copper tubes mechanically expanded into blue hydrophilic aluminum fins.
Refrigerant circuit complete with charge valves, filter drier, sight glass, gas-liquid separator, thermostatic expansion valve, high & low pressure switch. The Heat Pump System unit is completed also with 4-way valve, liquid receiver and one way valve.
Hydraulic circuit built with galvanized pipe, complete with water discharge connection for tube in tube heat exchanger and flange type hydraulic connectors in two directions easy for connections from both sides of the units.
Electric panel consist of:
Compressor contactor, fan motor contactor, compressor protection breaker, fan protection breaker, phase sequence relay and microprocessor with function display (display only for master/packaged unit)
Automatic operation dramatically reducing maintenance cost thanks to reliable microprocessor system.
Optional
Paddle flow switch;
Metallic filter for hydraulic circuit;
Water pump;
Rubber antivibration mounting;
Heat recovery functions.
Technical Data
Model AW | 60 | 100 | 130 | 200 | 260 | ||
Cooling capacity* | kW | 65 | 97.5 | 130 | 195 | 260 | |
Cooling power input | kW | 20.8 | 31.4 | 42.1 | 63.6 | 84.2 | |
Heating capacity** | kW | 68 | 102 | 136 | 204 | 272 | |
Heating power input | kW | 20.2 | 30.6 | 41 | 61.2 | 82 | |
Max Input Power | kW | 24 | 35.7 | 47.7 | 71.4 | 95.4 | |
Max Input current | A | 50 | 74 | 97 | 148 | 194 | |
Cooling Running Current | A | 46 | 68 | 89 | 136 | 178 | |
Start-Up Current | A | 167 | 187 | 206 | 374 | 412 | |
Compressor | |||||||
Power supply | / | 380/3/50 | |||||
Brand/Type | / | Daikin/Scroll | |||||
Refrigerant | / | R410a | |||||
Qty/refrigerant circuit | Nr. | 2 | 3 | 4 | 6 | 8 | |
Cooling power input* | kW | 2*9.4 | 3*9.63 | 4*9.77 | 6*9.63 | 8*9.77 | |
Heating power input** | kW | 2*9.1 | 3*9.36 | 4*9.5 | 6*9.36 | 8*9.5 | |
Energy adjustment | % | 0-25-50-75-100 | |||||
Axial fan | |||||||
Quantity | Nr. | 2 | 2 | 2 | 4 | 4 | |
Power input | kW | 2 | 2.5 | 3 | 5 | 6 | |
Airflow | m3/h | 24000 | 36000 | 48000 | 72000 | 96000 | |
Evaporator | |||||||
Type | / | Shell and tube heat exchanger | |||||
Water flow when cooling | m3/h | 11.2 | 16.8 | 22.4 | 33.6 | 44.8 | |
Water flow when heating | m3/h | 11.7 | 17.6 | 23.4 | 35.1 | 46.8 | |
Water side pressure drop *** | kPa | 46 | 52 | 55 | 52 | 55 | |
Water connection size | DN | 50 | 50 | 65 | 2x50 | 2x65 | |
Noise level*** | dB(A) | 70 | 72 | 72 | 74 | 75 | |
Dimensions | |||||||
V type coil | Length | mm | 2000 | 2207 | 2207 | 2207 | 2207 |
Width | mm | 1060 | 1300 | 1300 | 2207 | 2207 | |
Height | mm | 1957 | 2076 | 2076 | 2096 | 2096 | |
Net weight | kg | 620 | 1060 | 1120 | 2160 | 2280 | |
Working weight | kg | 635 | 1090 | 1155 | 2220 | 2350 |
Product Categories : Water Chiller > Glycol Water Chiller
Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.
Fill in more information so that we can get in touch with you faster
Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.