Model No.()KM

BrandAmrta or OEM

TypeCentral Air Conditioners

Indoor Machine Noise<23dB

CertificationCE

China Energy Efficiency StandardLevel 1

Cooling/HeatingCooling/Heating

Power SourceElectrical

ConditionNew

Operating Voltage220-240V, 50/60Hz

Application FieldsOffice, Home, Villa And Resterant Etc

MountingCeiling Mount

Supply Ability & Additional Information

PackagingPlywood Casing

Productivity10000PCS/Year

TransportationOcean,Air

Place of OriginChina

Supply Ability10000PCS/Month

HS Code8415830000

PortQingdao,Shandong,China

Payment TypeL/C,T/T,Western Union

IncotermFOB,CFR,CIF

Packaging & Delivery
Selling Units:
Set/Sets
Package Type:
Plywood Casing

Ultra thin Chilled Water Fan Coil Units are based on the forced convection heat transfer technology which makes the heat dissipation more efficient, compared with the traditional heating radiators, the Fan Coil units can save more than 30% energy consumption. The advanced control makes uniform temperature distribution and people feel more comfortable. When combined with Heat Pump System units, the fan coil units can meet different heating or cooling requirements. With low noiseonly 25dB (A)and ultra thin casing 130mm, the units stand out of the terminals markets.


Product Description
Efficient and Energy Saving
Efficient ABS blower which is light weighted while statically and dynamically balanced.
Excellent thinwall copper tube and efficient hydrophilic aluminum fin are under water pressure bonded treatment. Patent inverse crossing circuit to reach the best heat transfer efficiency. Brass water distributor is used for improving water flow distribution, in order to provide better heat transfer effect. 
Quiet Operation
Low noise and permanent capacity motor, unique ABS centrifugal blower, all of them pass dynamically balance test, to ensure unit operate quietly and efficiently.
3-speed motor, ball bearing, long lifespan; rubber vibration isolator reduces operation noise.
Stable and Reliable
U-shaped tube bending, reducing soldered dot and leakage point.  
Drain pan is made of high grade stainless steel plate, modeling processing; surface has been under hot dipped electroforming painting treatment. 7mm PE thermal insulation foam is applied on the drain pan to prevent condensation and leakage from occurring. Furthermore the width and length of the drain pan has been specifically designed to accommodate the water drop from the water inlet / outlet and electrically operated valve.There is fuse in power supply inlet side to prevent motor burned because of wrong wiring. Reliable and stable motor which enjoys good reputation in the market.
Different Models
Static pressure: 12Pa, 30Pa, 50Pa.
Fan coil unit series: horizontal exposed type, horizontal concealed type, vertical concealed type, vertical exposed type, cassette type, large air volume fan coil unit.
Accessories: 3-speed switch, return air box, extended drain pan, electronic two-way valve, electrical heater, air cleansing module.
All above are for your selection.

Performance Parameter

Model

34KM

51KM

68KM

85KM

102KM

136KM

170KM

204KM

238KM

 

Air flow [m3/h]

H

340

510

680

850

1020

1360

1700

2040

2380

M

280

390

520

640

790

1030

1290

1500

1800

L

180

260

350

430

520

690

860

1030

1200

Total cooling capacity *

[W]

H

2000

3000

3700

5000

5600

7300

9900

11000

12800

Heating capacity *  [W]

H

3000

4800

5500

7200

8200

10800

14500

16800

19200

Fan motor

 

 

 

 

 

 

 

 

 

 

Nominal power input

W

37

52

62

76

96

132

152

189

220

Nominal current input

A

0.162

0.23

0.276

0.338

0.417

0.588

0.663

0.824

0.976

Water flow rate

m3/h

0.42

0.522

0.62

0.86

0.98

1.22

1.58

1.92

2.2

Water pressure drop

kPa

14

14

16

18

22

25

39

44

44

Water connections

inch

ZG 3/4``

Drain pipe

mm

26

 

Sound pressure level **

[dB(A)]

H

37

39

41

43

45

46

47

50

52

M

34

36

38

39

42

43

44

46

48

L

30

32

35

36

38

39

40

42

44

Net Dimension W/D/H 

mm

Unit

580*580*290

710*710*290

832*832*290

Panel

680*680*30

830*830*30

980*980*30

Power supply

/

220V/1Ph/50Hz

 

Net weight

 kg

Unit

25

25

26

28

29

29

36

38

38

Panel

2.5

4

5

Note:* The data are referred to the following conditions:
Cooling: room temperature: 27 ºC, DB / 19.5 ºC WB; water temperature: 7/12 ºC, high speed.
Heating: room temperature: 21 ºC, water inlet temperature: 70 ºC, high speed. Water flow rate same as in cooling operation.
** Sound pressure measured in anechoic room 1.5 m away from the unit.

Chilled Water Exposed Fan Coil Unit

Product Categories : Fan Coil > Exposed Fan Coil

Download
Home > Products > Fan Coil > Exposed Fan Coil > Ultra Thin Floor Standing Exposed Fan Coil Unit
Email to this supplier
  • *Subject:
  • *To:
    Mr. Richard Lee
  • *Email:
  • *Message:
    Your message must be between 20-8000 characters
Send Inquiry
*
*

Related Products List

Home

Product

Whatsapp

About Us

Inquiry

We will contact you immediately

Fill in more information so that we can get in touch with you faster

Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.

Send